Critical Environment Technologies Canada Inc. www.critical-environment.com Installation Manual for AST-IS5 Analog transmitters with Infrared CO2 &am
10 ITEM LOCATORS 1 top portion 2 lid 3 front portion 4 wall plate 5 screw 6 label with settings inside the top portion DRAWING #1 INSTALLING THE TRA
11 INSTALLING THE TRANSMITTER, CONT’D….. REMOVE THE SECURING SCREW FROM THE TOP PORTION, ITEM-5 IN ITEM LOCATOR ON PREVIOUS PAGE PULL THE TOP PORTION
12 INSTALLING THE TRANSMITTER, CONT’D….. SECURE THE WALL PLATE WITH SCREWS. MAXIMUM SCREW HEAD DIAM-TER SHOULD BE 7.5 mm. MAXIMUM SCREW HEAD HEIGHT SH
13 INSTALLING THE TRANSMITTER, CONT’D….. THE TOP PORTION IS PUSHED UNDER THE LOCKING HOOKS OF THE WALL PLATE AND IS SECURED WITH A SCREW TERMINALS &am
14 WIRING TERMINALS & SIGNAL OUTPUT JUMPER SETTINGS OUT-2 OUT-1 + POWER 24VAC / DC+ POWER GROUND (-) ANALOG OUT 4-20mA(+) CO2 ANALOG OUT 2-10VDC
15 Connection Terminal Function Electrical Data Remarks G+ G0 Power (+) Power ground (-) 24 VAC/DC+ (+-20%), 3W 24 VAC/DC- 2W w
16 AST20150224-C-AST-IS5-Manual-Rev-C Critical Environment Technologies Canada Inc. Unit 145, 7391 Vantage Way, Delta, BC, V4G 1M3, Canada Toll Free:
2 This product is in accordance with EMC 2004/108/EC, 92/31/EEG including amendments by the CE-marking Directive
3 IMPORTANT NOTE Read and understand this manual prior to using this instrument. Carefully read the warranty policy, service policy, notices, disclaim
4 Due to ongoing research, development, and product testing, the manufacturer re-serves the right to change specifications without notice. The informa
5 national and domestic copyright laws, this manual may not be copied or translated, in whole or in part, in any manner or format, without the written
6 AST-IS5 ANALOG TRANSMITTER with INFRARED CO2 SENSOR & TEMPERATURE SENSOR and LCD DIGITAL DISPLAY The AST-IS series are reliable, long li
7 FUNCTIONAL DESCRIPTION OUT-1 = Measuring signal of CO2 concentration lowest value - highest value. OUT-2 = Measuring signal of temperature lowest v
8 TECHNICAL SPECIFICATIONS GAS TYPE Carbon Dioxide (CO2) MECHANICAL Enclosure General Purpose PVC., IP30 rated Size 4.7” x 3.2” x 1.2” (120mm x 8
9 TERMINAL DEFAULT OUTPUT DEFAULT OUTPUT RANGE OUTPUTS OF THIS SENSOR OUTPUT RANGE OF THIS SENSOR OUT-1 4-20 mA 0-2000 ppm CO2 OUT-2 2-10 VDC