9
TERMINAL DEFAULT
OUTPUT
DEFAULT
OUTPUT
RANGE
OUTPUTS OF
THIS SENSOR
OUTPUT
RANGE OF
THIS SENSOR
OUT-1 4-20 mA 0-2000 ppm CO
2
OUT-2 2-10 VDC 0 - 50
o
C
RELAY Closed
Open
>1000 ppm CO
2
<900 ppm CO
2
DEFAULT OUTPUT CONFIGURATION FOR AST-IS5
Configuration Output Range Formula for Calculation
0-10 VDC 0-2000 ppm CO
2
0 - 50
o
C
CO
2
value = Volt / 10 * 2000
Temperature value in C = Volt / 10 * 50
2-10 VDC 0-2000 ppm CO
2
0 - 50
o
C
CCO
2
value = (Volt-2) / 8 * 2000
Temperature value in C = (Volt-2) / 8 * 50
4-20 mA 0-2000 ppm CO
2
0 - 50
o
C
CO2 value = (nA-4) * 2000 / 16
Temperature value in C = (mA-4) * 50 / 16
a-b c-d Value = (reading-a) / (b-a) * (d-c) + c
a = lowest value of the configuration
b = highest value of the configuration
c = lowest value of the range
d = highest value of the range
FORMULAS FOR CALCULATING OUTPUT VALUES
NOTE: RED LED is lit when the relay output is closed.
OUTPUT CONFIGURATIONS
JUMPER POSITION FUNCTION
Start point
selection jumper
0%
20%
Jumper top position provides 0VDC or 0mA start point
for OUT-1, OUT-2 (0-20 mA or 0-10 VDC)
Jumper bottom position provides 2VDC or 4mA start
point for OUT-1, OUT-2 (4-20 mA or 2-10 VDC)
OUT-1 Current
Voltage
Connection in position “Current” provides 0/4-20 mA
output range for OUT-1
Connection in position “Voltage” provides 0/2-10 VDC
output range for OUT-1
OUT-2 Current
Voltage
Connection in position “Current” provides 0/4-20 mA
output range for OUT-2
Connection in position “Voltage” provides 0/2-10 VDC
output range for OUT-2